This Part of EN 1366 specifies a method of test and criteria for the evaluation (including field of application rules) of the ability of a penetration seal to maintain the fire resistance of a separating element at the position at which it has been penetrated by a service. Penetration seals used to seal gaps around chimneys, air ventilation systems, fire rated ventilation ducts, fire rated service ducts, shafts and smoke extraction ducts are excluded from this standard except for mixed penetration seals. The fire resistance of those services itself cannot be assessed with the methods described in this standard. Supporting constructions are used in this standard to represent separating elements such as walls or floors. These simulate the interaction between the test specimen and the separating element into which the sealing system is to be installed in practice. This European Standard is used in conjunction with EN 1363-1. The purpose of this test described in this standard is to assess: a) the effect of such penetrations on the integrity and insulation performance of the separating element concerned; b) the integrity and insulation performance of the penetration seal; c) the insulation performance of the penetrating service or services, and where necessary, the integrity failure of a service. No information can be implied by the test concerning the influence of the inclusion of such penetrations and sealing systems on the loadbearing capacity of the separating element. It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes. Such phenomena are only to be noted in describing the general behaviour of test specimens during the test. This test is not intended to supply any information on the ability of the penetration seal to withstand stress caused by movements or displacements of the penetrating services. The risk of spread of fire downwards caused by burning material, which drips through a pipe downwards to floors below, cannot be assessed with this test. Explanatory notes to this test method are given in Annex H. All dimensions given without tolerances are nominal ones unless otherwise stated.
Số hiệu tiêu chuẩn
EN 1366-3
Tên tiêu chuẩn
Fire resistance tests for service installations - Part 3: Penetration seals
Ngày phát hành
2009-02-00
Tiêu chuẩn tương đương
DIN EN 1366-3 (2009-07), IDT * BS EN 1366-3 (2009-03-31), IDT * NF P92-130-3 (2012-11-01), IDT * SN EN 1366-3 (2009), IDT * OENORM EN 1366-3 (2009-05-01), IDT * PN-EN 1366-3 (2009-04-22), IDT * PN-EN 1366-3 (2010-01-13), IDT * SS-EN 1366-3 (2009-03-09), IDT * UNE-EN 1366-3 (2011-02-23), IDT * UNI EN 1366-3:2009 (2009-05-07), IDT * STN EN 1366-3 (2009-08-01), IDT * CSN EN 1366-3 (2009-09-01), IDT * DS/EN 1366-3 (2009-06-22), IDT * NEN-EN 1366-3:2009 en (2009-03-01), IDT * SFS-EN 1366-3:en (2009-04-17), IDT
Tiêu chuẩn liên quan
EN 520 (2004-11) *
EN 1363-2 (1999-08) *
EN ISO 13943 (2000-04) * EN 1363-1 (1999-08) * EN 1452-1 (1999-06) * EN 1453-1 (2000-01) * EN 1455-1 (1999-07) * EN 1519-1 (1999-07) * EN 1565-1 (1998-12) * EN 1566-1 (1998-12) * EN 1992-1-2 (2004-12) * EN 1996-1-2 (2005-05) * EN 10305-4 (2003-04) * EN 10305-6 (2005-05) * EN 12201-2 (2003-03) * EN 12449 (1999-07) * EN 12666-1+A1 (2011-08) * EN 13501-1+A1 (2009-09) * EN 13501-2+A1 (2009-09) * EN 13600 (2002-03) * EN 61386-21 (2004-02) * HD 21.3 S3 (1995-02) * HD 22.4 S4 (2004-03) * HD 603.3 * HD 604.5
Từ khóa
Building component test * Components * Conditioning * Construction * Definitions * Enclosure of space * Evaluations * Fire resistance * Fire safety * Fire tests * Installations * Pipe valve * Scarfing * Sealing * Seals * Seals for cable penetrations * Shielding * Structural fire protection * Surface spread of flame * Test reports * Test specimens * Testing * Testing conditions * Thermal insulation * Thermocouples * Gaskets